C3552 Datasheet

Power Misc: Rack And Cabinet Mounting Converters: Indust

Download: C3552 Datasheet C3552 datasheet
Stock & Ordering: Octopart | Findchips
C3552
Power Misc: Rack And Cabinet Mounting Converters: Indust
Rack & Cabinet Mounting Converters
C SERIES
150-12 k Watts
CE Marked - LVD & EMC
Over 1700 Different Models
DC Inputs 10 - 900 Volts
Single & Multi Outputs
Fully Wired Customised Racks
Parallel Redundant Systems
Euro Cassette or Wall Mount
Specification
Voltage Range No-load Input Current Switch-on Time Hold-up Time Inrush Current High-energy
Pulses/surges Spikes/bursts Line Regulation ( 10%) Load Regulation (10-90%) Ripple Load Transient
(20-100-20%) Response time to 1% Overload protection Overvoltage protection
Remote Sensing Temperature Coefficient Operating Temperature Storage Temperature Relative Humidity
Efficiency At Full Load Switching Frequency Isolation Voltage Emc M.t.b.f. Construction (safety)
Creepage distance Air distance Connector
See Tables of models, unit switches off at under- and overvoltage
3% of full load current typical
100 ms typical - C300-C4700, 500 ms typical - C5600-C5800
Depends on input voltage (typ. 2 ms at 12 V DC)
Depends on impedance of supply line, see list of options for option 'I'
ENV 50142 (level 3)
Acc. to IEC 1000-4-4 (level 3)
1% + 30 mV p-p (0.5% typical lin. reg. aux.)
6% typical
2 ms typical - C300-C4700, 10 ms typical - C5600-C5800
Current limited at 105-110% of full load (See Technical Notes s/c protection)
Standard on single output models and main output on multi output units
OVP switches off module with automatic restart
Standard on main output and all single outputs
0.02%/ C typical
-20 C to +75 C derate from +55 C at 2.5%/ C (Optional -40 C to +75 C)
-40 C to +85 C
5 to 95% Non Condensing
60-90%, depending on model
Approx. 33 kHz